Add to Cart
SUN2000-50KTL-ZHM3 | ||
Technical Specifications | ||
Efficiency | ||
Max. Efficiency | 98.5% | |
European Efficiency | 98% | |
Input | ||
Max. Input Voltage | 1,100 V | |
Max. Current per MPPT | 30 A | |
Max. Short Circuit Current per MPPT | 40 A | |
Start Voltage | 200 V | |
MPPT Operating Voltage Range | 200 V ~ 1,000 V | |
Rated Input Voltage | 600 V | |
Number of Inputs | 8 | |
Number of MPP Trackers | 4 | |
Output | ||
Rated AC Active Power | 50,000 W | |
Max. AC Apparent Power | 55,000 VA | |
Rated Output Voltage | 380 Vac ,3W / (N)+ PE | |
Rated AC Grid Frequency | 50 Hz / 60 Hz | |
Rated Output Current | 76.0A/380Vac | |
Max. Output Current | 84.0A/380Vac | |
Adjustable Power Factor Range | 0.8 LG ... 0.8 LD | |
Max. Total Harmonic Distortion | <3% | |
Protection | ||
Input-side Disconnection Device | Yes | |
Anti-islanding Protection | Yes | |
AC Overcurrent Protection | Yes | |
DC Reverse-polarity Protection | Yes | |
PV-array String Fault Monitoring | Yes | |
DC Surge Arrester | Type II | |
AC Surge Arrester | Type II | |
DC Insulation Resistance Detection | Yes | |
Residual Current Monitoring Unit | Yes | |
Communication | ||
Display | LED Indicators, Bluetooth + APP | |
USB | Yes | |
RS485 | Yes | |
Monitoring BUS (MBUS) | Yes (isolation transformer required) | |
General Data | ||
Dimensions (W x H x D) | 640*530*270 mm | |
Weight (with mounting plate) | 49 kg | |
Operating Temperature Range | -25°C ~ 60°C (-13°F ~ 140°F) | |
Cooling Method | Natural Convection | |
Max. Operating Altitude | 4,000 m (13,123 ft.) | |
Relative Humidity | 0 ~ 100% | |
DC Connector | Amphenol Helios H4 | |
AC Connector | Cable Gland + OT Terminal | |
Protection Degree | IP65 | |
Topology | Transformerless | |
Nighttime Power Consumption | < 2 W | |
Country of Manufacture | China | |
Standard Compliance (more available uponrequest) | ||
Certificate | N/IEC 62109-1, EN/IEC 62109-2, IEC 62116 | |
Grid Code | AS/NZS 4777.2 2020 |